LINE TANDEM MODEL CONSISTING OF QTY 2 6DH*3500 COMPRESSORS
Unit of Measure

Specifications

Catalog Number

N/A CPE-86T

CFH 60 Hz

N/A 9060

Model

N/A Line Tandem

Net Weight (lbs)

N/A 560

Nominal HP

N/A 70

Oil Charge (oz.)

N/A 280, 260

Ship Weight (lbs)

N/A 1040

Consisting of Two Models

N/A 6DH-3500

Notes

Note

N/A No. 1 or No. 2 preceeding model A or B indicates R-12 or R-22. Rebuilt compressors are interchangeable.

R after model number indicates right hand compressors on Tandem unit unloader control and oil equalizer lines on the reverse side. This is the only difference. A-Letter may be B-C-D-E, which is design sequence.

Evacuation Procedure

N/A

 
System Cleanliness
 
System cleanliness is one of the most important factors that affect system and compressor reliability. System contamination can cause both mechanical and electrical failures. There are several sources ofsystem contamination. Some of these are:
  1. Copper oxides from system refrigerant piping brazing.
  2. Refrigerant piping chips and burrs and brazing flux.
  3. Processing residue and metal chips from evaporators and condensers.
  4. Metal chips and wire brush strands from processing of other system components.
  5. Contamination in refrigeration tubing which is left uncapped during assembly.
  6. Moisture and air.
    In addition, field erected systems are subject to all the dirt and system contamination of the typical jobsite. It is recommended that a suction line filter be installed in the system to prevent contaminants form entering the compressor ;
 

 
Evacuation and Dehydration
 
For the refrigeration system to work property, it must be free of air and moisture. The process by which air and moisture are removed is known as evacuation and dehydration. Moisture and air are harmful to the system because they increase the condensing temperature, raise the discharge gas temperature, cause oil breakdown and the formation of acids. Acids are corrosive to the components in the refrigeration system, including the piping, refrigerant specialties, and the which can cause mechanical failure of the compressor.

The recommended method for evacuation and dehydration is to evacuate the system from both the gigh and low sides to 800 microns or less. To establish that the unit is leakfree and moisture-free, a standing vacuum test is recommended. The maximum allowable rise over a 15 minute period is 200 microns. If the Hse exceeds this, either there is still moisture in teh system or a leak is present in the system See Chart 1.

CAUTION
NEVER USE OXYGEN OR ACETYLENE IN PLACE OF REFRIGERANT AND DRY NITROGEN FOR LEAK TESTING. A VIOLENT EXPLOSION MAY RESULT, CAUSING PERSONAL INJURY OR DEATH.

ALWAYS USE A PRESSURE REGULATOR WHEN USING NITROGEN TO PRESSURE TEST. FAILURE TO DO SO WILL RESULT IN EXTREMELY HIGH PRESSURE WHICH COULD EXCEED THE BURST PRESSURE OF TEH COMPRESSOR OR OTHER SYSTEM COMPONENTS AND RESULT IN PERSONAL INJURY OR DEATH.

FOR SHELF STORAGE EVAC. TO 250 MICRONS

Accessories

Accessories

N/A , Pumps
, Crankcase Heaters
, Crankcase Heaters
, Accessories
, Unloaders
, Accessories
, Terminal Plates & Parts
, Terminal Plates & Parts
, Valve Plates & Parts
, Valve Plates & Parts
, Gaskets
, Accessories
, Accessories
, Accessories
, Accessories
, Accessories